ICT Intelligent Dual Bus DC Load Distribution Panels

Breaker Panel, Supports Dual-Voltage Inputs and Mixed Polarities

MSRP
$1,500.00  
CAD
|

SKU

ICT200DB-12IRC

Weight

8.6 lb

Stock Quantity

2 CAN

The Distribution Series 3 from ICT is a dual-bus DC distribution panel designed to be used in 12-, 24- or 48-volt DC applications. This dual-bus panel can support dual-voltage inputs and mixed polarities and is available with either fuse- or circuit breaker-protected outputs. Models include a secure, easy-to-use web-browser interface, which provides remote power monitoring, power control, and alarm reporting over an Ethernet link, along with SNMP support for integration into your network management system.

The ICT Distribution Series 3 provides independent dual bus capability for redundant systems or mixed-voltage sites. Each bus is rated at 100A peak and provides six fuse or breaker protected outputs. Standard models are available for unmanaged applications, while Intelligent models include ICT’s industry leading TCP/IP remote management and power control features.

Product Features:
  • 200A peak system current rating / 100A per bus
  • Six outputs per bus
  • Independent Form C alarm contacts for each bus
  • Choice of fuse or breaker protected models
  • Mixed voltages and polarities can be supported in one panel (provided grounds are common)
  • Front panel LED indicators for fuse status (fuse models)
  • 2 year warranty
Intelligent Model Features:
  • TCP/IP remote management and power control of system and individual outputs
  • On-board web server means no software to maintain
  • Remote firmware update capability
  • HTTPS, SMTP, SNMP protocols supported
  • Monitoring and alarm reporting of each output for pinpointing of issues with connected loads
  • Alarms can be sent to multiple email accounts
  • Each output has adjustable load-shed settings
  • Five digital inputs for site monitoring sensors
  • Data logging
  • Password protection
Product Includes:
  • ICT Intelligent Dual Bus Breaker Panel (Distribution Series 3)

Specifications:

Power Specifications
Application Voltage (pos or neg gnd) 12, 24, 48VDC
System Current Rating (peak/cont) 200A / 160A
Bus Current Rating (peak/cont) 100A / 80A
Number of Outputs per bus 6
Operating Voltage Range 10-60VDC
Number of Breaker Outputs 12
Max Breaker Ratings (12, 24V) 30A
Max Breaker Ratings (48V) 20A
Mechanical
Form Factor 1RU - 19 Inch rack mount with handles
Dimensions (inches) L x W x H 9.29 x 19.0 x 1.72
Weight (lbs/kg) 7.0lbs / 3.2kg
Connectors M8 DC input stud connectors, 10-22AWG cage clamp output terminal blocks
Environmental
Operating Temperature Range -30C to +60C
Communication and Control
Ethernet TCP/IP built-in web server and graphical user interface, 10/100BASE-T, IEEE 802.3 compatible
Supported Protocols IPv4, HTTP, HTTPS, SMTP, DNS, TCP, UDP, ICMP, DHCP, ARP, SNMP v1/v2c/v3
SNMP Ports UDP Port 161, SNMP Traps: UDP Port 162
Firmware Upgrades Upgradeable over Ethernet
Security Password protected, HTTPS encryption, TLS 1.0
12 Channel Output Monitoring Current draw measured and reported for each output, user definable under and over current alarms
Email and SMS Alerts Multiple email or text accounts, adjustable intervals
Data Logging Up to 30 days at 1 minute sampling rate, csv file download, major event logging
Network Watchdog Autonomously ping up to two I.P. addresses and power-cycle output if no response, definable settings
Power Cycling and Rebooting Remote on/off control of every output individually
Auto Restore Mode Return to previous output settings after a power loss
Power-up Delay Sequencing User selectable 0 to 60 second delay between outputs
Auto Load Shedding Each output user definable, manual or auto restart
Remote Alarms Independent Form C alarm contacts (C/NO/NC)